DPT-Flow is a flow transmitter that provides a solid and easy way to measure the flow rate on centrifugal fans.

This device is a versatile flow transmitter which is usable for a vast range of different fan types.

 

 

Price:

94,08 129,47  +VAT: 21%

D= display
AZ=autozero
-40c = cold-resist model

Description

DPT-Flow

This device is a versatile flow transmitter which is usable for a vast range of different fan types. It also provides an easy way to measure flow rate in a duct system. The device is supplied with an optional FloXactTM averaging measurement probe.

 Applications

The DPT-Flow is designed for air handling units to measure the air flow on the centrifugal fans.

You can use DPT-FLOW with a local display to measure the flow or use as a transmitter to program and regulate the airflow on a specific blower or fan.

Another application of DPT-FLOW is in the duct system or air handling units. The type with display provides you the possibility to read the flow at the moment and locally. It can also be used as a transmitter to regulate the airflow in the duct.

DPT-FLOW can be combined with different measurement probes such as FloXactTM or pitot tube and air dampers. In this case, it is important to know the value of the K parameter for probe or damper.

Here you can find the table to customise your order :

Additional information

Models

DPT Flow-1000, DPT Flow-2000, DPT Flow-5000, DPT Flow-7000

Different Configurations

DPT Flow-1000-D (BASIC MODEL), DPT Flow-1000-AZ-D, DPT-Flow-1000-D-40C, DPT Flow-2000-D (BASIC MODEL), DPT Flow-2000-AZ-D, DPT-Flow-2000-D-40C, DPT Flow-5000-D (BASIC MODEL), DPT Flow-5000-AZ-D, DPT-Flow-5000-D-40C, DPT Flow-7000-D (BASIC MODEL), DPT Flow-7000-AZ-D, DPT-Flow-7000-D-40C

Technical details
Accuracy (from applied pressure): (models 1000 and 2000) Pressure < 125 Pa = 1 % + ±2 Pa Pressure > 125 Pa = 1 % + ±1 Pa
Accuracy (from applied pressure): (models 5000 and 7000) Pressure < 125 Pa = 1.5 % + ±2 Pa Pressure > 125 Pa = 1.5 % + ±1 Pa
Zero point calibration: automatic with autozero element (-AZ) or by pushbutton
Measuring units: Pressure: Pa, kPa, mbar, inchWC, mmWC, psi Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
Supply voltage: 24 VAC ±10 % / 24 VDC ±10 %
Power consumption: < 1,0 W
Output signals for pressure and air flow (selectable by jumper): 0…10 VDC / 2...10 VDC 4…20 mA
Operating temperature: -20…+50 °C (with autozero calibration -5...+50 °C) -40...+50 °C (-40C model)
Response time: 1...20 s
Protection standard: IP54