Multifunctional CO2 transmitters for building automation systems

3 devices in 1, separate field configurable output for each measurement parameter (CO2, rH, T)

Price:

163.45 217.00  +VAT: 21%

D=display
1R=relay
rH=relative humidity
DC= dual Channel sensor

Description

CDT2000

CDT series air quality transmitters are designed for building automation systems in the HVAC/R industry. The CDT series is able to measure carbon dioxide (CO2) and temperature (T) at the same time. The industry standard NDIR measurement principle is used for measuring carbon dioxide. If you want to measure the relative humidity (rH), you can the option to this device and will measure all three parameters at the same time. Having a large touchscreen display, provides an easy and accurate configuration for the user. 

The CDT2000 series transmitters calibrate themselves automatically using ABC logicTM. The ABC logicTM (Automatic Background Calibration algorithm) requires that the space in which the transmitter is used needs to be unoccupied for four hours per day so that the indoor CO2 concentration drops to the outside level. CDT2000-DC is a dual channel model with a measuring channel and a reference channel that makes a continuous comparison and the necessary adjustment accordingly. CDT2000-DC has a premium advantage for buildings that are continuously occupied.

CDT series devices include:

  • Separate field configurable output for each measurement parameter (CO2, rH, T)
  • Proportional output options including: voltage (0–10 V, 2–10 V) and current (4–20 mA)
  • Offset feature enabling field calibration for each measurement parameter (CO2, rH, T)
  • Time extension button that enables boosting ventilation manually using the touchscreen display (models with relay)

CDT2000 series device options:

  • 2” x 3” touchscreen display
  • Field configurable relay for any of the three parameters
  • Modbus configuration

 

Here you can find the table to customise your order :

Additional information

Models

CDT2000, CDT2000-DC

Different Configurations

CDT2000 (BASIC MODEL), CDT2000-D, CDT2000-1R-D, CDT2000-rH, CDT2000-rH-D, CDT2000-1R-rH-D, CDT2000-DC (BASIC MODEL), CDT2000-DC-D, CDT2000-DC-1R-D, CDT2000-DC-rH, CDT2000-DC-rH-D, CDT2000-DC-1R-rH-D

Technical details
Accuracy: CO2: ±40 ppm + 2 % of reading, DC model: 75 ppm or 10 % of reading (whichever is greater) Temperature: <0.5 °C Relative humidity: ±2…3 % rH at 0…50 °C and 10…90 % rH Total error band includes accuracy, hysteresis and temperature effect over 5...50 °C and 10–90 % rH
Measurement elements: Temperature sensor: Pt1000 / Integrated (models with rH-measurement), Non-Dispersive Infrared (NDIR) CO2 sensor, thermoset polymer capacitive sensing element for humidity
Measuring units: ppm, °C, % rH
Calibration: Automatic self-calibration, ABC LogicTM or continuous comparison (DC)
Supply voltage: 24 VDC/VAC ±10 %
Output signal 1: 0/2…10 V or 4…20 mA (linear to CO2) (2–10 V output: display required)
Optional output signal 2: 0/2…10 V or 4…20 mA (linear to rH) (2–10 V output: display required)
Output signal 3: 0/2…10 V or 4…20 mA (linear to Temp) (2–10 V output: display required)
Optional relay output: Potential free SPDT 250 VAC, 6 A / 30 VDC, 6 A with adjustable switching point and hysteresis
Operating temperature: 0...50°C
Protection standard: IP20
 